发表状态 | 已发表Published |
题名 | Optimisation of Direct Expansion (DX) Cooling Coils Aiming to Building Energy Efficiency |
作者 | |
发表日期 | 2015 |
发表期刊 | Journal of Building Construction and Planning Research
![]() |
ISSN/eISSN | 2328-4889 |
卷号 | 3期号:2页码:47-59 |
摘要 | Efficient Air Conditioning (A/C) system is the key to reducing energy consumption in building operation. In order to decrease the energy consumption in an A/C system, a method to calculate the optimal tube row number of a direct expansion (DX) cooling coil for minimizing the entropy generation in the DX cooling which functioned as evaporator in the A/C system was developed. The optimal tube row numbers were determined based on the entropy generation minimization (EGM) approach. Parametric studies were conducted to demonstrate the application of the analytical calculation method. Optimal tube row number for different air mass flow rates, inlet air temperatures and sensible cooling loads were investigated. It was found that the optimal tube row number of a DX cooling coil was in the range of 5 - 9 under normal operating conditions. The optimal tube row number was less when the mass flow rate and inlet air temperature were increased. The tube row number increased when the sensible cooling load was increased. The exergy loss when using a non-optimal and optimal tube row numbers was compared to show the advantage of using the optimal tube row number. The decrease of exery loss ranged from around 24% to 70%. Therefore the new analytical method developed in this paper offers a good practice guide for the design of DX cooling coils for energy conservation. |
关键词 | Optimal Tube Row Number Entropy Generation Minimization Direct Expansion (DX) Cooling Coil Building Energy Efficiency |
DOI | 10.4236/jbcpr.2015.32006 |
URL | 查看来源 |
语种 | 英语English |
引用统计 | |
文献类型 | 期刊论文 |
条目标识符 | https://repository.uic.edu.cn/handle/39GCC9TT/12002 |
专题 | 个人在本单位外知识产出 |
通讯作者 | Xia, Liang |
作者单位 | 1.Department of Architecture and Built Environment, University of Nottingham Ningbo China, Ningbo, China 2.School of Mathematical Sciences, University of Nottingham Ningbo China, Ningbo, China 3.Department of Civil Engineering, University of Nottingham Ningbo China, Ningbo, China |
推荐引用方式 GB/T 7714 | Xia, Liang,Yang, Tong,Chan, Yueet al. Optimisation of Direct Expansion (DX) Cooling Coils Aiming to Building Energy Efficiency[J]. Journal of Building Construction and Planning Research, 2015, 3(2): 47-59. |
APA | Xia, Liang, Yang, Tong, Chan, Yue, Tang, Llewellyn, & Chen, Yung-Tsang. (2015). Optimisation of Direct Expansion (DX) Cooling Coils Aiming to Building Energy Efficiency. Journal of Building Construction and Planning Research, 3(2), 47-59. |
MLA | Xia, Liang,et al."Optimisation of Direct Expansion (DX) Cooling Coils Aiming to Building Energy Efficiency". Journal of Building Construction and Planning Research 3.2(2015): 47-59. |
条目包含的文件 | 条目无相关文件。 |
个性服务 |
查看访问统计 |
谷歌学术 |
谷歌学术中相似的文章 |
[Xia, Liang]的文章 |
[Yang, Tong]的文章 |
[Chan, Yue]的文章 |
百度学术 |
百度学术中相似的文章 |
[Xia, Liang]的文章 |
[Yang, Tong]的文章 |
[Chan, Yue]的文章 |
必应学术 |
必应学术中相似的文章 |
[Xia, Liang]的文章 |
[Yang, Tong]的文章 |
[Chan, Yue]的文章 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论